Network UPS Tools (NUT)

The nut package (shown as Network UPS Tools in the Package Manager) integrates Network UPS Tools to monitor an uninterruptible power supply. It supports a UPS connected directly to the firewall over USB or serial, and remote UPS units reached through another NUT server, apcupsd, the netxml protocol, or SNMP. When the UPS reports a critical low-battery condition, FreeSense shuts itself down cleanly.

At the 1.1.0 release lock the package (FreeSense-pkg-nut 2.8.2_12) depends on NUT 2.8.5 from the pinned FreeBSD ports tree.

Use it on any firewall that runs on a UPS, so that a long power cut ends in a clean shutdown instead of a crash and a possibly damaged file system.

  1. Open System → Package Manager → Available Packages.
  2. Find Network UPS Tools (category System, lightweight) and select Install package, then Confirm.

Stable packages are published for amd64 and, starting with 1.1.1, arm64. See Installing packages.

Menu path Page
Services → UPS (Monitoring group) UPS Status tab: summary and full UPS variable list
Services → UPS → UPS Settings UPS type, driver, and advanced configuration
Dashboard UPS Status widget

The service appears as nut (UPS monitoring daemon) under Status → Services.

The example below covers the most common case, a UPS connected by USB.

  1. Connect the UPS USB cable to the firewall.
  2. Open Services → UPS and select the UPS Settings tab.
  3. Set UPS Type to Local USB.
  4. Enter a UPS Name, for example ups (letters, digits, _ and - only).
  5. Select a Driver. usbhid (usbhid-ups) works for most current UPS models; check the NUT Hardware Compatibility List linked under the field if unsure.
  6. Optionally select Enable notifications under Notifcations to receive e-mail or other alerts on power events.
  7. Select Save. You are taken to the UPS Status tab.
  8. Check that Summary status shows On line and that battery charge and runtime are reported.
  9. Add the UPS Status widget to the dashboard if wanted.

For a UPS that another server monitors, choose Remote NUT server, enter the server’s address, the UPS name as configured on that server, and a NUT user name and password that the server accepts.

Field What it does Default
UPS Type Disabled, Local USB, Local serial, Local serial (genericups), Remote NUT server, Remote apcupsd, Remote netxml, Remote snmp, or Dummy UPS. Disabled stops NUT and removes its generated files while keeping the entered values. Disabled
UPS Name Name of the UPS (required unless disabled); [a-zA-Z0-9_-] only. For Remote NUT server it must match the name on the remote server. Empty
Notifcations → E-Mail Enable notifications sends power events (online, on battery, low battery, forced shutdown, communication lost/restored, shutdown, replace battery, no communication, no parent) to the methods configured under System → Advanced → Notifications. Off

The fields shown depend on UPS Type.

Field Used by What it does
Driver (USB) Local USB USB driver: usbhid, apc_modbus, bcmxcp, blazer, atcl, qx, richcomm, riello, tripplite. The port is set to auto.
Driver (serial) Local serial Serial driver, for example apcsmart, bcmxcp, blazer, powerpanel, qx, tripplite, victronups, and others from NUT.
Serial port Local serial, genericups Detected /dev/cuau* and /dev/cuaU* devices.
Generic Ups Type genericups upstype value for contact-closure UPS cables, 0-22.
Remote protocol Remote netxml http or https.
Remote IP address or hostname Remote NUT, apcupsd, netxml, snmp Address of the remote server or UPS network card.
Remote port (optional) Remote NUT, apcupsd, netxml Non-default port.
Remote username / Remote password Remote NUT (required), netxml Credentials for the remote server.
Dummy port Dummy UPS File or host definition used by the dummy-ups driver, useful for testing.
Extra Arguments to driver (optional) Local and remote driver types Additional ups.conf lines for this UPS, one per line, for example community=private or snmp_version=v2c for SNMP, or pollinterval=15.

Select Display Advanced to show these fields. Each adds raw lines to the generated NUT file.

Field Appended to Notes
Additional configuration lines for upsmon.conf upsmon.conf All types, for example FINALDELAY or DEADTIME.
Additional configuration lines for ups.conf Top of ups.conf (global section) Local and driver-based remote types.
Additional configuration lines for upsd.conf upsd.conf For example additional LISTEN lines so other hosts can use this UPS.
Additional configuration lines for upsd.users upsd.users Users for other NUT clients.

FreeSense generates the rest itself: upsd listens on 127.0.0.1 and ::1 only, and the local monitor connects as an internal local-monitor user with a random password that changes on every save.

  • Local USB or serial UPS: no rules needed.
  • Remote NUT, apcupsd, netxml, or SNMP: the firewall connects outward to the remote server or UPS card (NUT uses TCP 3493, apcupsd TCP 3551, SNMP UDP 161 by default). Make sure that path is open on any device in between.
  • To let other hosts monitor a UPS attached to the firewall, add a LISTEN line for an interface address in the upsd.conf field, add a user with upsmon secondary (or upsmon slave) in the upsd.users field, and add a pass rule for TCP 3493 from those hosts on that interface. Keep this on a trusted network.
Item Value
Service nut (status follows upsmon)
rc script /usr/local/etc/rc.d/nut.sh starts the driver (upsdrvctl), upsd, and upsmon for local and driver-based types, or only upsmon for Remote NUT server
Shutdown hook /usr/local/etc/rc.d/shutdown.nut.sh, run at system shutdown; if upsmon -K reports a forced shutdown, it tells the UPS to cut power (upsdrvctl shutdown)
Configuration /usr/local/etc/nut/ups.conf, upsd.conf, upsd.users, upsmon.conf (generated, do not edit)
Shutdown command /sbin/shutdown -p +0, with power-down flag /etc/killpower
State directory /var/db/nut (recreated automatically, also after a RAM-disk boot)
Status page Services → UPS: name, summary status, alarm, runtime, load, battery charge and voltage, input voltage and frequency, last test result, and all variables from upsc
Widget UPS Status, with load and battery bars and an alert when the UPS needs attention
Logs NUT events go to the system log (Status → System Logs); package messages use the NUT prefix

The summary status translates NUT flags into words: On line, On battery, Low battery, Charging, Discharging, Replace battery, Overloaded, Bypass, Calibrating, Voltage trim, Voltage boost. On battery, low battery, replace battery, bypass, overload, or any UPS alarm raise an alert on the status page and widget.

  • Settings are stored in config.xml under installedpackages/nut and are included in configuration backups. The remote password is stored in the configuration, so protect backups.
  • Configurations from the older NUT package format (with a monitor setting) are migrated when the settings page is opened; a warning asks you to review and save.
  • Removing the package stops NUT and deletes the generated configuration files, rc script, and shutdown hook.
Symptom Cause and fix
UPS name cannot be empty / Name may contain [a-zA-Z0-9_-] only Enter a simple name such as ups.
Remote IP Address / Host must be a valid IP address or hostname Correct the remote address.
Remote username cannot be empty / Remote password cannot be empty Remote NUT servers require both.
UPS Monitor pending Shown during the first minute after boot. Wait.
UPS Daemon pending The local upsd started less than a minute ago. Wait and refresh.
UPS Monitor not running upsmon is stopped. Check Status → System Logs, then start nut under Status → Services.
Failed to retrieve status The driver cannot talk to the UPS. Try another driver, check the cable and USB port, and add driver options in Extra Arguments to driver. For SNMP, check the community string and version.
Serial port list is empty No /dev/cuau* or /dev/cuaU* device is present; check the cable or USB-serial adapter.
No notifications Enable notifications in the package and configure a method under System → Advanced → Notifications.
Firewall shut down but the UPS kept power Some UPS models ignore the power-off command or need driver options (for example offdelay). Test the full shutdown sequence during a maintenance window.